For a richer surfing experience on our website, please update your browser. Update my browser now!
This project presents a whole-building energy performance study for a G+11 hospitality building in Vadodara, Gujarat—classified as a hot-and-dry coastal climate under ECBC. The work methodically optimizes the building envelope (shading, walls, roof), HVAC systems, and humidity control strategies, followed by the integration of rooftop solar PV, to minimize the Energy Performance Index while maintaining or enhancing indoor comfort. Key interventions include climate-responsive shading design, upgraded insulated envelope assemblies, high-efficiency VSD centrifugal chillers, AHU-based dehumidification for humidity-sensitive areas, and on-site PV generation. Collectively, these measures reduce the EPI from an ECBC-compliant baseline of about 217 kWh/m²·year to approximately 149 kWh/m²·year. Comfort increases to nearly 98% of occupied hours within the target temperature and relative-humidity range, and the optimized envelope also lowers embodied carbon. Although the final design package increases initial capital cost slightly, it delivers strong NPV and ROI, with a payback period of under three years—demonstrating a technically sound and economically compelling pathway to low-energy hotel design in a demanding hot and dry context.