This project is a whole-building energy performance study for a G+11 hospitality building in Visakhapatnam, Andhra Pradesh, located in a warm–humid coastal climate as per ECBC. The work sequentially optimizes envelope (shading, walls, roof), HVAC systems, and humidity control, and then integrates rooftop solar PV to minimize Energy Performance Index while maintaining or improving comfort. Key strategies are climate-driven shading device design, improved insulated assemblies, high-efficiency VRF and centrifugal chillers with VSDs, AHU-based dehumidification for humidity-intensive zones, and PV for on-site generation. Across these measures, the design reduces EPI from an ECBC-compliant baseline of roughly 221 kWh/m²·year to around 186 kWh/m²·year, while increasing comfort to about 98% of occupied hours within the desired temperature and RH band and cutting embodied carbon of the optimized envelope. The final package slightly increases CAPEX but offers strong NPV, ROI, and a payback of under three years, demonstrating a technically and economically robust approach to low-energy hotel design in a challenging warm–humid climate.