This report outlines a comprehensive strategy to enhance the energy performance of an 11-storey hotel in Mysore using a top-down approach across envelope and HVAC systems. A combination of advanced methods — including multi-objective envelope optimization and EMS-based supervisory HVAC control — reduced the Energy Performance Index from 164 to 117 kWh/m²·year, and further to 107 kWh/m²·year with renewable integration. Cooling and equipment loads formed 60% of baseline energy use, guiding optimization toward envelope improvements. Sensitivity analysis highlighted wall and glazing gains as key drivers, leading to cost-effective envelope designs that cut cooling load and reduced embodied carbon by 68%. Daylighting was enhanced using chamfered overhangs compliant with ECBC. Two HVAC proposals were evaluated; the water-cooled chiller with thermal storage and supplementary ECMs yielded the best performance. Financially, Proposal 2 with RE achieved the highest NPV (16 crore), offering the most balanced long-term solution.


Report Content

Climate analysis & Evaluation of Passive strategy potential

Thermal load assessment & Zoning strategy

Optimizing daylight performance of the hotel

Envelope optimization based on Capex & Thermal performance trade-off

Low-cost Energy Conservation Measure - Changeover Mixed mode operation

Water-Side Energy Conservation Measures

ASHRAE 36-High Performance Control Sequence

Air-Side Energy Conservation Measures

Renewable energy integration & Upfront Embodied carbon assessment

Holistic Assessment of all proposals