Dafda Jaydip Dharamshibhai

BE4003

IDL & WBD I Monsoon Semester 2026

This project is a mixed-use commercial building in Jodhpur, designed to cut energy demand while keeping occupants comfortable in a hot, dry climate. Using whole-building simulation, a standard-practice case was compared with an improved design that combines shading, heat recovery, better zoning and plant sizing, and efficient VRF systems. The final design brings energy use down from 143.4 to 105.4 kWh/m²/year, and to 99.2 kWh/m²/year with rooftop solar. The work also covers daylight performance, life-cycle carbon, and cost, and shows that the measures are practical and financially sound under ECSBC 2024.


Report Content

Climate analysis and standard case baseline

Shading devices and daylight

Load analysis and zoning strategy

HVAC system type and plant sizing

HVAC optimization, water side

HVAC optimization, air side

Natural ventilation, mixed mode and comfort

Solar PV integration

Life-cycle carbon assessment

Cost analysis and final proposed case summary