Swasti Agrawal

BE4003

IDL & WBD I Monsoon Semester 2026

This study evaluates building energy performance, thermal comfort, life-cycle economics, and embodied carbon for a 41,560 m2 commercial office and retail development (3-basements +G+21) in Gangtok's cold climate using DesignBuilder and EnergyPlus. After correcting the window-to-wall ratio from 40% to 48%, passive envelope optimization (RockWool insulation, SHGC tuning, and exterior shading) offsets solar and conductive penalties. Active HVAC interventions—integrating a heat pump, adaptive setpoints, hydronic VAV reheat with supply air reset, and differential enthalpy economizer control—reduce the Energy Performance Index from 134.06kWh/m2.yr to 71.55 kWh/m2.yr (46.62% reduction), while lowering upfront capital costs and generating positive 50-year Net Present Value.


Report Content

Climate Analysis & Natural Ventilation Potential

Daylight Optimization & Orientation Specific Shading

Base Case HVAC system description

Envelope Optimization as per Super ECSBC

HVAC Optimization (ECM - System selection)

HVAC Optimization (ECM - VAV system upgradation, AHU temperature reset, economizer optimization)

Summary of Energy Conservation Measures

Cost Benefit Analysis

Life Cycle Analysis