For a richer surfing experience on our website, please update your browser. Update my browser now!
The IDL & WBD studio focused on improving the energy performance of a Ground + 21 commercial building in Raipur, combining retail and offices, through an integrated whole-building approach. An ECSBC 2024 standard case was modelled in DesignBuilder, followed by climate analysis, orientation-specific shading with daylight checks (UDI), and HVAC optimization using asymmetric, sequenced chillers. Energy conservation measures (ERV, demand-controlled ventilation, lighting power density reduction and chilled water reset) were tested one at a time and then combined. Together they reduced EPI from 134.65 to 89.45 kWh/m²·year (33.6%), supported by embodied carbon and 50-year cost-benefit analyses.