Vedika N D

BE4003

IDL & WBD Lab | Monsoon Semester 2026

This project studies the energy performance of a G+21 mixed-use building in Jaipur's composite climate, using EnergyPlus simulation. Starting from an ECSBC 2024 Standard case with an Energy Performance Index (EPI) of 143.8 kWh/m²·yr, the design is refined through climate analysis, envelope optimisation, passive strategies, daylight assessment and a right-sized HVAC system with sequenced chillers, energy recovery and evaporative cooling. The final case, without thermal storage, reaches an EPI of 91.7 kWh/m²·yr, a 36% reduction (82.1 with rooftop solar PV), and cuts HVAC electricity by 42%. On assumed costs, the package repays its extra investment within a year.


Report Content

Building Context & Climate Analysis

ECSBC Standard case & Daylight Analysis

Envelope Optimisation: Glazing, Roof and Wall

Passive Strategy potential in Jaipur's Context

Selection of HVAC system

Proposed case HVAC System

Standard case vs Proposed case HVAC comparison

Rooftop Solar: Sizing & Carbon Benefit

Cost Benefit & Life-Cycle Analysis

ECSBC Compliance check & Summary