This portfolio evaluates the energy performance of a 21-storey mixed-use office tower in Agra (composite climate) using DesignBuilder. Radiative gains (35%) dominate, so the study tests envelope ECMs (low-E glazing, shading), lighting dimming, ERW, VSD, and chiller staging, then compares VRF and radiant alternatives. The selected ECM-enhanced water-cooled VAV cuts EPI from 109.98 to 87.94 kWh/m²·yr (?20%) and unmet hours from 298 to 126. Rooftop PV (211 kWp) adds 7% of supply; the 50-year NPV is positive from year 0.