Nikitha Dileep

BE4003

Monsoon Semester 2026 | IDL & WBD Studio

Pragya 02 is a commercial tower in Visakhapatnam: 3 basements + G+20, 41,000 m² gross, 28,000 m² air-conditioned, in the Warm and Humid zone. The problem is moisture, not heat. 98.7% of hours have a dew point above 15 °C, 70–80% of coil load is latent, and natural ventilation works in only 0.6% of hours. The strategy is therefore to shade selectively, remove moisture efficiently, and stop over-cooling. The proposed design for Pragya 02 cuts the Energy Performance Index (EPI) from 129.22 to 79.45 kWh/m² (38.5% lower), costs about Rs 1.09 crore less to build than the standard case and returns a 50-year net present value of Rs 40.0 crore. 


Report Content

01 | The Climate Challenge: Defining Visakhapatnam’s high humidity and limits on natural ventilation.

02 | Baseline & Zoning: Deconstructing Pragya 02’s thermal zoning and dominant latent loads.

03 | Passive Shading: Sculpting the facade to cut solar exposure while preserving daylight.

04 | High-Performance Envelope: Pairing premium SNX 60+ glazing with heavy AAC walls to flatten daytime heat spikes.

05 | Roof & Plant Synergy: Capping with reflective roofing and driving down energy via 50-50 chiller sequencing.

06 | Advanced HVAC: Integrating ERWs to aggressively strip moisture and eliminate reheat coils.

07 | System Efficiency: Raising chilled water to 8°C, culminating in a 38.5% EPI reduction.

08 | Solar PV: Achieving 48.4% usable roof area for a 580W bifacial array, offsetting 5.62% of building electricity.

09 | Life Cycle Trade-Off: The "carbon debt"—investing high upfront embodied carbon for massive operational savings.

10 | 50-Year Cost-Benefit: Proving economic viability with positive Year-0 cash flow and robust NPV.