Greywater Reuse Network for Data Centre Cooling

This project designs, calculates and tests a gravity-driven greywater network that collects used water from six outlets and supplies it to a data centre as cooling make-up water, with fresh-water backup. Hardy Cross flows were checked in WaterGEMS, a Manning sewer was designed, and a working model was tested live.

View Additional Work

Report Content

Pressure drops where velocity rises, shown on a Venturi rig and in a CFD simulation of a ventilated chimney.

Modified Hazen-Williams predicts the field pipeline's head losses best, with the lowest RMSE for both the 1/2-inch UPVC and 1-inch CPVC pipes.

A quadruple loop network balanced by iteration

Rectangular, V and trapezium notches tested to relate head to discharge and find their Cd values (0.8, 0.7 and 0.6).

A 56-junction, 1 km² water network designed and checked, with pressure above 7 m at every junction.

The question is whether greywater from nearby buildings can serve as cooling water for a data centre.

A scaled working greywater network, drawn in AutoCAD, modelled in SketchUp, checked in WaterGEMS and built and tested on site.

The hand-calculated flows agree closely with WaterGEMS, while live outlet flows drift from the design.

Six gravity sewer lines that run partly full (d/D 0.26–0.38) and work as open channels.

The model built on site, from fixing tanks and fitting channels to the finished pipe grid tested live.