Shubh Bansal

AR3596

UAR21128

This research project assesses thermal comfort in Studio 25b, a low-energy office building in Ahmedabad designed by Kakani Associates. The building uses a hybrid Downdraught Evaporative Cooling system and no conventional air conditioning. Environmental monitoring across winter and summer seasons was combined with 158 occupant perception surveys. Results were evaluated against the PMV/PPD model and India's adaptive comfort standard, IMAC. Findings show the system maintains indoor temperatures approximately 6°C below outdoor peaks, with occupants reporting acceptable comfort despite PMV overpredicting discomfort. The study supports wider adoption of passive cooling strategies in Indian office buildings.

View Additional Work

Report Content

Research Overview

Introduction

Methodology

Literature Review : Downdraught Evaporative Cooling

Case Study Building : Studio 25b

Quantitative data collection

Thermal Perception Survey

Results and Analysis

Comparison with IMAC model

Conclusion and Discussion