Pargaonkar Ishwari Sanjay

BE4003

IDL and WBD Lab | Monsoon Semester 2025

The IDL and WBD studio centered on improving the energy performance of Club O7, a G+11 hotel in Hyderabad, using an integrated whole-building design methodology. A Standard Case model was first developed in accordance with ECBC 2017, after which systematic optimization was carried out including building envelope optimization, daylight compliance, and HVAC system evaluation to minimize thermal loads and enhance overall system efficiency. The study also explored mixed-mode ventilation, adaptive HVAC strategies, and rooftop solar PV integration. The iterative optimization process demonstrated a clear performance improvement from the Standard Case EPI of 213.16 kWh/m²·year to the Proposed Case EPI of 149 kWh/m²·year, achieving a 30% reduction. Each ECM was evaluated against key performance indicators (KPIs) such as unmet comfort hours, thermal gains, system efficiency, and whole-life operational impact.


Report Content

Introduction and climate analysis

Daylight compliance

Standard case performance

Building envelope optimization

HVAC system selection

HVAC system optimization

Renewable energy integration

Life cycle assessment

Cost benefit analysis

Final performance summary