For a richer surfing experience on our website, please update your browser. Update my browser now!
This report outlines a comprehensive strategy to enhance the energy performance of an 11-storey hotel in Mysore using a top-down approach across envelope and HVAC systems. A combination of advanced methods — including multi-objective envelope optimization and EMS-based supervisory HVAC control — reduced the Energy Performance Index from 164 to 117 kWh/m²·year, and further to 107 kWh/m²·year with renewable integration. Cooling and equipment loads formed 60% of baseline energy use, guiding optimization toward envelope improvements. Sensitivity analysis highlighted wall and glazing gains as key drivers, leading to cost-effective envelope designs that cut cooling load and reduced embodied carbon by 68%. Daylighting was enhanced using chamfered overhangs compliant with ECBC. Two HVAC proposals were evaluated; the water-cooled chiller with thermal storage and supplementary ECMs yielded the best performance. Financially, Proposal 2 with RE achieved the highest NPV (16 crore), offering the most balanced long-term solution.