Jogi Niyati Jayesh

BE4003

Monsoon Semester 2024 | IDL & WBD Lab

The project showcases a whole building energy performance optimization of a 11-storey hotel located in Bangalore, India. Designed for 24-hour operation, the building exhibits diverse load patterns across its podium facilities and upper guestroom floors. The study enhances thermal and visual comfort through envelope optimization, efficient HVAC configuration and renewable integration. Envelope optimization focused on the thermal transmittance (U-value) of walls and glazing, addressing the most sensitive elements influencing heat transfer and indoor comfort. Moreover, sequential HVAC optimization from Variable refrigerant flow (VRF) to hybrid VRF-Variable air volume (VAV) systems with zone-level control reduced unmet hours while improving system efficiency. Among all energy conservation measures, improving VRF unit efficiency and incorporating zone-level Fan coil units (FCU) proved the most effective. The final integration of a 274-panel solar PV system enabled a 7% energy offset. Collectively, the measures reduced EPI from 149.1 to 133.15 kWh/m²·yr, showcasing building performance improvement.


Report Content

Climate analysis

Daylight performance optimization

Envelope optimization

Low energy cooling strategies and mixed mode operation

Standard design case

HVAC optimization

Renewable integration

Cost benefit and Life cycle analysis

Cost analysis

Summary